PTTS-H008-0-02M
类型: Fail-Safe Transfer
品牌: Server Technology
型号: PTTS-H008-0-02M
产品详情

产品简介

The Sentry Fail-Safe Transfer Switch (FSTS) features two input power feeds, from separate AC circuits, to supply single-power equipment with dual, redundant power sources. A primary AC circuit provides power to the connected device(s). With this rack automatic transfer switch, if the primary source becomes unavailable for whatever reason, then the Sentry FSTS auto-switches to the secondary power source to support the connected equipment.

The transfer from one power source to the other is seamless to the connected equipment with this rack automatic transfer switch. When the secondary power source is available, an interruption of the primary power source will not affect the equipment's uptime or performance.

Unique to the Sentry FSTS is the ability to designate which power source is primary and which is secondary. With the Primary Select switch, a power engineer simply toggles the switch from primary to secondary, which transfers the load from one power feed to the other. Now, the "secondary" becomes "primary" and the power engineer can safely work on the first power source without dropping power to the connected equipment.

产品特点

Sentry  Cabinet PDU Specifications
Item #Available Input
Voltages

Rated

Amperage

Available Input CordOutletsDimensions
(L x W x D)
Fail-Safe Transfer Switch CDU
PTTS-H008-0-02M*100-120V
50/60Hz
or
208-240V
50/60Hz
20A
or
16A
NEMA 5-20P,
L5-20P or
IEC 60320/C13
Cord Set, 10 ft (3m)
(8) IEC 60320/C13

1.75" x 8" x 17"
(44x203x432mm)

*Power Cords Sold Separately
Additional Features and Specifications
Standards
> cTUVus ? UL 60950-1-2003
> CAN/CSA 22.2 No. 60950-1:2003
> TUVGS ? EN 60950-1:2001
> FCC Class A, Part 15
> CE
> EMC-EN 55022 Class A, EN 55024

Branch Circuit Protection
>Compliant to UL 60905-1
Fail-Safe redundancy between Primary and Secondary power sources.
Primary-Select switch to designate primary power source;
Range-Select switch to designate operating range (voltage).
Transfer Range
Nominal Pull In Drop Out 110-120V 90V 12V 208-230V 173V23V
Indicator LEDs-Confirms power supplied to outlets
-Identifies condition as primary power source or secondary power source supplying power to outlets
Voltage Range Select-Supplies either 100-120V or 208-230V AC voltage ranges
-120V and 230V equipment cannot be intermixed
-All power input feeds must be removed prior to selecting/altering operating range
-Remove Range Select faceplate covering to select appropriate voltage
-Lucite window allows visual confirmation of voltage range
-Switch in ?up? position designates 208/230V
-Switch in ?down? position indicates 110/120V
Mechanical Integrity-Dual-brace cable retainer brackets on power input feeds
-Clip-style cable-retention retainer brackets at each power outlet receptacle
-Adjustable mounting for front or rear panel, flush or recessed mounting