STV-6503J
类型: 智能PDU
品牌: Server Technology
型号: STV-6503J
产品详情

产品简介

The Server Technology® PRO2 Switched POPS CDU provides control of outlet power and local LED input current monitoring, allowing IT personnel to determine safe levels of loading on a per-phase basis while installing equipment into the rack/cabinet. The integral PIPS® and POPS® technology provides billing-grade accurate measurement of current, voltage, active power, apparent power, power factor, crest factor, and accumulated energy at the input and at each output. These power data points, along with temperature and humidity measurements (provided via optional probes), are accessible through the built-in Web and CLI interfaces as well as through SNMP. The PRO2 Switched POPS "Master" CDU can be connected to as many as three PRO2 Switched POPS "Link" CDUs to extend the network access to the redundant or secondary power feed without the risks of a daisy chain linking conguration.

产品特点

Sentry Cabinet PDU Specifications
Master CDU
Link CDUInput Current
Input Plug
Input Voltage
Rated Power
Global
STV-6503JSEV-6503J
≤ 16A
IEC 60309 6hr
3P+N+PE Red, 3m,
5-C, H05VV-F, 4.0mm²
220V-240V, L-N,
50/60Hz
11 kW @230V
STV-6503K
SEV-6503K
≤ 32A
IEC 60309 6hr
3P+N+PE Red, 3m,
5-C, H05VV-F, 4.0mm²
220V-240V, L-N, 50/60Hz
22 kW @230V
Additional Features and Specifications
Outputs
• Connector: (24) x IEC 60320/C13
• Global Rating (C13):  10A @220-240V
• Connector: (6) x IEC 60320/C19
• Global Rating (C19):  16A @220-240V
• LockedIn™ compatible. Locking outlets provide high-retention even for non-locking cords

Input measurement accuracy
• LED Current = ± 10% 0.1 amp (1.0 – 9.9amps) and 1 amp (>9.9amps) resolution
• GUI Current = ± 1% at 0.01 amp resolution (above 0.5 amp)
• Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%)
• Active Power = ± 1% at 1 watt resolution
• Apparent Power = ± 1% at 1 volt-amp resolution
• Power Factor = ± 3% at 0.01 resolution
• Crest Factor = ± 10% at 0.1 resolution
• Energy = ± 1% at 0.1 kilowatt-hour resolution

Output measurement accuracy
• Current = ± 1% at 0.01 amp resolution (above 0.5 amp)
• Voltage = ± 1% at 0.1 volt resolution (nominal +/-10%)
• Active Power = ± 1% at 1 watt resolution
• Apparent Power = ± 1% at 1 volt-amp resolution
• Power Factor = ± 3% at 0.01 resolution
• Crest Factor = ± 10% at 0.1 resolution
• Energy = ± 1% at 1 watt-hour resolution

Branch measurement accuracy
• Current = ± 3% at 0.01 amp resolution (above 0.5 amp)

Branch Circuit Protection
• UL489 compliant 1-pole, 20A trip circuit breakers, Six (6) branches, Rating:  16A @220-240V

Physical/Environmental
• Dimensions: 70.00" (1778 mm) tall x 2.19" (56 mm) wide x 2.25" (57 mm) deep | Weight: 25 lbs (11.4 kg)
• Shipping Dimensions: 73" x 7" x 3" (186 cm x 18 cm x 8 cm) | Weight: 26 lbs (11.8 kg)
• Highlight Color: Choose Black, White, Red, Green, Blue, Yellow
• Operating Environment: 32°F to 140°F / 0°C to 60°C | 8%RH to 90%RH non-condensing | 6,500ft/2000m elevation
• Storage Environment: -40°F to 185°F / -40°C to 85°C | 8%RH to 90%RH non-condensing | 50,000ft/15km elevation
• Quiescent / Unloaded Power Draw: < 10W for all configurations

Communications and Security
• 10/100 Mbps Ethernet (RJ-45 connector), RS-232 serial (RJ-45 connector)
• Two (2) temperature/humidity sensor inputs (4P4C), Link port (RJ-12) – {also on Link CDU}
• Web-browser GUI and command-line-interface (CLI): HTTP/HTTPS, SSLv3/TLSv1, SSHv2, Telnet, SNMPv2c and v3
(GET, SET, Traps), IPv4 and IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, FTP/SFTP

Certifications
• TUV T-Mark to EN 60950-1:2006 + A11 + A1 + A12
• EMC to EN 55022 Class A, EN 55024, CISPR 22 Class A
• CE Mark
• RoHS/WEEE

Optional Accessories
• EMTH-1-1 Combination Temperature/Humidity Probe, 10ft (3m)
• EMCU-1-1B Environmental Monitor adding:
- Two (2) EMTH-1-1 temperature/humidity ports (one probe included)
- One (1) EMWS-1-1 water sensor port (probe sold separately)
- Four (4) dry contact (NO/NC) monitoring points
- One (1) 8-bit analog-to-digital converter (0 to 5VDC)
• SPM (Sentry® Power Manager):
- Monitor and manage multiple PDUs from a single point
- Monitor and manage alarm conditions
- Create reports and trends on stored data
- Analyze power usage per phase
- Optional appliance or virtual version
- VMware Ready2
• Mounting Brackets
- Buttons (KIT-0020) included for tool-less mounting (see diagram).
- See the Mounting Bracket Guide for further suggestions.
- Custom mounting options available. Contact your local Server Technology representative.
• Cable Retention Devices for non-locking cords
- EZip
- Cable Sleeve
- Wire Bails
• Device / Output LockedIn™ Power Cords
- UL Rated, or VDE Rated


Sentry  Cabinet PDU Features

Network Monitoring
The PRO2 hot-swappable network card provides for HTTP(S), SSH, Telnet,SNMP, (S)FTP, SMTP, Syslog, LDAP(S), RS-232 serial, and more.

Branch Current Monitoring
PRO2 monitors current at each breaker branch and provides SNMP-based alerts and emails on high usage that risks a tripped circuit.

Star Multi-Linking
PRO2 provides the ability to link up to four power circuits using one IP
address. Primary link provides backup power to network card.

Branch Circuit Protection
PRO2 meets the UL and IEC 60950-1 requirement for branch circuit protection
through use of UL489 rated magnetic-hydraulic circuit breakers.

Hot-Swap Network Card
Network access is ensured when power is lost to the Master unit with
backup power provided by the primary link unit.

ST Eye Bluetooth Ready
The best CDU LCD is the one in your hand. Attach the ST Eye™ Bluetooth
module to PRO2 for access to power data and system settings.

Temperature/Humidity Monitoring
PRO2 Master and Link units each support two external 10' (3m) T/H
probes. Receive SNMP-based alerts and email notifications.

High Retention Locking Outlets
PRO2 receptacles have high retention and are compatible with Server Technology's LockedIn™ power cords (sold separately).

Outlet Control
On PRO2 Switched CDUs, cycle power to individual outlets or groups of
outlets to reboot servers. Or, power off unused receptacles.

Power Pivot™
The 90 degree rotatable power cord allows for standardized deployment
at any facility no matter where power must be routed.

Auto-ip Current Display
Easy-to-read LEDs display current per phase to help prevent overloads and
simplify three-phase load balancing in high-density cabinets.

Flexible Mounting
PRO2 includes standard button mounts along with provisions for
custom mounting brackets (contact Server Technology for details).

Per-Inlet Power Sensing
Meets ANSI C12.1 for billing-grade accuracy of Current per phase. PIPS
includes voltage, active power, apparent power, power factor, and energy.

High Temperature Rating
This product has been tested and approved for safe and reliable operation
in 60°C (140°F) data center environments.

Per-Outlet Power Sensing
Meets ANSI C12.1 for billing-grade accuracy of Current per outlet. POPS includes voltage, active power, apparent power, power factor, and energy.

Color Identification
Choose from six colors to designate circuits for CDUs in the data center.
Color options include Blue, Red, Green, White, Yellow, and Black.

Cisco EnergyWise* Compliant
PRO2 meets the requirements set forth by Cisco System, Inc. for its EnergyWise program for monitoring of device energy.